Understanding footstep and impact noise isolation
IIC (Impact Insulation Class) rates how well a floor-ceiling assembly blocks impact noise โ footsteps, dropped objects, moving furniture. Higher IIC = less noise transmitted to the floor below.
There is exactly one requirement here, and it is short. IBC 2021 ยง1206.3 applies to floor-ceiling assemblies separating dwelling units and sleeping units from each other or from public and service areas:
| How it is established | Rating | Test method |
|---|---|---|
| Laboratory test | IIC not less than 50 | ASTM E492 |
| Field test | NISR not less than 45 | ASTM E1007 |
Impact insulation is not required over non-habitable spaces โ garages, mechanical rooms, storage. The section also allows the rating to be established by engineering analysis comparing assemblies with E492 ratings, rather than by testing the specific assembly.
Figures you will see quoted for luxury condominiums, hotels, senior housing or units above retail โ IIC 55, 60, 65 โ are design conventions and client standards, not code. We could not attribute any of them to a published requirement, so this guide does not present them as minimums. If a project needs one, it comes from the specification, not from the building code.
A standardized "tapping machine" with 5 hammers strikes the floor 10 times per second. Sound levels are measured in the room below at 16 frequencies (100-3150 Hz). These ISPL (Impact Sound Pressure Level) values are compared against a reference contour to calculate IIC.
Similar to STC, but for impact noise:
The most effective single intervention. Soft materials absorb impact energy before it enters the structure.
| Floor Covering | ฮI IIC Improvement |
|---|---|
| Carpet + thick pad | +20 to +30 |
| Carpet + thin pad | +15 to +20 |
| Cork flooring (1/4") | +8 to +12 |
| Rubber underlayment + LVP | +5 to +15 |
| Hard tile / hardwood (no pad) | +0 to +3 |
A subfloor layer that "floats" on resilient material, not rigidly attached to the structure.
Adding isolation to the ceiling below can significantly help.
Heavier floor structures perform better:
| Assembly | IIC |
|---|---|
| Wood joist + 3/4" subfloor + hardwood + drywall ceiling | 25-32 |
| Above + carpet/pad | 48-55 |
| Wood joist + resilient channel ceiling + insulation | 35-42 |
| Above + carpet/pad | 55-65 |
| 6" concrete slab + hardwood | 28-35 |
| 6" concrete + floating floor + carpet | 55-65 |
| Concrete + gypcrete topping + carpet + suspended ceiling | 60-70 |
Replacing carpet with hardwood or tile can drop IIC by 15-25 points. Many condo associations require IIC testing or specify minimum underlayment when changing floor finishes.
Impact vibration travels through:
Field IIC is often limited by flanking even when the direct path is well isolated.
Standard IIC testing starts at 100 Hz, but heavy footfalls and dropped objects create energy below that. Some assemblies test well but still transmit annoying low-frequency "thump." Extended frequency ratings (IIC-L) capture this.
Select a common assembly type to see typical IIC performance. Use this for quick estimates during planning.
Enter ISPL values from a lab test (ASTM E492) or field test (ASTM E1007) to calculate exact IIC. Lab reports provide ISPL at each frequency.
Use the curve comparison feature to visually compare up to 6 different floor assemblies side-by-side: